ELECTRICAL FORMULAS
COMMONLY USED
ELECTRICAL FORMULAS

To Obtain

SINGLE PHASE
(Alternating Current)

THREE PHASE
(Alternating Current)

Kilowatts

V x l x pf

1000

1.732 x V x l x pf

1000

kV•A

V x l

1000

1.732 x V x l

1000

Amperes
(kW known)
kW x 1000

V x pf

kW x 1000

1.732 x V x pf

Amperes
(motor hp known)
hp x 0.746

V x pf x Efficiency
hp x 0.746

1.732 x V x pf x Efficiency
Amperes
(kV•A known)
kV•A x 1000

V
kV•A x 1000

1.732 x V
Horsepower
(kW unknown)
kW

0.746 x Efficiency
(Generator)
kW

0.746 x Efficiency
(Generator)
Horsepower
(generator efficiency unknown)
kW

0.746 x 0.93
kW

0.746 x 0.93
kW input
(motor hp known)
hp x 0.746

Efficiency
(Motor)
hp x 0.746

Efficiency
(Motor)
kW input (motor efficiency? unknown) hp x 0.85 hp x 0.85